Fluke 1630-2 Earth Ground Clamp Meter

Fluke 1630-2 Earth Ground Clamp is placed around the earth ground rod or the connecting cable. A known voltage is induced by one half of the clamp and the current is measured by the other half. The earth ground clamp meter automatically determines the ground loop resistance at this grounding connection.

Applications: Tests earth ground



  HTTPS Secured PaymentHTTPS, the lock icon in the address bar, an encrypted website connection. While it was once reserved primarily for passwords and other sensitive data, the entire web is gradually leaving HTTP behind and switching to HTTPS. The 'S' in HTTPS stands for 'Secure'. It’s the secure version of the standard “hypertext transfer protocol”. Most importantly, your payment is also secured.

   Bulk Purchase? Reach us for special price
  Free shipping all over India
  Ask a question?

Product Description

Fluke 1630-2 Earth Ground Clamp Meter is a very compact and rugged design that makes it easy to use in small places and harsh environments and hard to reach places. The display hold and the continuity testing feature with an audible alarm function ensures Ease of use. The earth ground loop testing and continuity testing can be completed without breaking the circuit using the novel technique.

Features Of Fluke Earth Ground Clamp Meter:

  • A wide ground loop resistance ranges from 0.025 Ω to 1500 Ω
  • Large jaw opening of 35 mm (1.38 in) for tests on ground conductors and equipotential bus bars
  • Measurement of ground leakage current ranges from 0.2 mA to 1000 mA, without need to disconnect -ideal for system troubleshooting
  • Wide ac current measurement range from 0.2 A to 30 A that allows one instrument for multiple applications
  • User-defined HI / LO Alarm limits, for Fast measurement evaluation
  • Automatic self-calibration
  • Overload protection: 200 A
  • ≥ 8 hours of battery life (continuous operation)
Electrical Specifications
Maximum voltage to earth ground 1000 V
Display reading specification with standard loop resistance
Input (Ω) Minimum Maximum
0.474 0.417 0.531
0.5 0.443 0.558
10 9.55 10.45
100 96 104
Earth Ground Loop Resistance
Range Accuracy1  ± (% of reading + Ω)
0.025 Ω to 0.249 Ω 1.5% + 0.02 Ω
0.250 Ω to 0.999 Ω 1.5% + 0.05 Ω
1.000 Ω to 9.999 Ω 1.5% + 0.10 Ω
10.00 Ω to 49.99 Ω 1.5% + 0.30 Ω
50.00 Ω to 99.99 Ω 1.5% + 0.50 Ω
100.0 Ω to 199.9 Ω 3.0% + 1.0 Ω
200.0 Ω to 399.9 Ω 5.0% + 5.0 Ω
400 Ω to 599 Ω 10.0% + 10 Ω
600 Ω to 1500 Ω 20.00%
1  Loop resistance with no inductance, conductor centered and perpendicular to jaw
Earth ground leakage current mA
Autorange 50/60 Hz, True rms, crest factor CF ≤3
Range Resolution Accuracy1  ± (% of reading + mA)
0.200 mA to 3.999 mA 1 μA 2.0% + 0.05 mA
4.00 mA to 39.99 mA 10 μA 2.0% + 0.03 mA
40.0 mA to 399.9 mA 100 μA 2.0% + 0.3 mA
0.400 A to 3.999 A 1 mA 2.0% + 3 mA
4.00 A to 39.99 A 10 mA 2.0% + 30 mA

Additional Information

Weight 2.5 kg
Manufacturer
Model No
Measuring Parameters Current, Frequency, Resistance, Temperature
Frequency
Temperature
Operating Temperature
Storage Temperature
Operating Humidity , ,
Operating Altitude
Storage Altitude
Protection class
Conductor Jaw Size
Emissivity
Battery
Battery Life
Safety
Dimensions
Weight

DS_Fluke 1630-2 Earth Ground Clamp Meter_Ver 1.0